9.3 On-load tap-changer regulator
9.3.1 Voltage regulation
All of the parameters required for the control function are described in this
section.
1. Go to
Settings > Parameters > On-load tap-changer regulator > Volt-
age regulation
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.
9.3.1.1 Setting the desired value
You can set three different desired values. The device always uses one of
the set desired values for control. You can define which desired value is
used for regulation with the "Change remote desired value setting" parame-
ter. You can define up to 3 desired values.
The device only processes commands via digital inputs or the control sys-
tem when it is in the Remote mode. You must also set the Remote behavior
[
Page 67] parameter accordingly.
Setting desired value 1...3
You can set the desired value with this parameter.
1. Go to
Settings > Parameters > On-load tap-changer > Voltage regula-
tion > Desired value
.
2. Enter the desired value.
3. Press the
Accept
button to save the modified parameter.
Changing the remote desired value setting
You can use this parameter to select the type of remote desired value set-
ting which the device is to use for regulation. You can select between 3 op-
tions:
▪ Remote desired value setting using 3 digital desired values
– For this option, make sure that the corresponding digital inputs are con-
nected.
▪ Remote desired value setting using analog desired values
– For this option, make sure that the corresponding analog input is con-
nected.
▪ Remote desired value setting using TDSC