9 Operation
Maschinenfabrik Reinhausen GmbH 2021
129
7817454/02 EN
TAPCON
®
230 Expert
You can select the following options:
Option
Description
Independent regula-
tion
The device switches from parallel operation to normal auto-
matic voltage regulation
Auto blocking
Automatic voltage regulation is blocked.
cosφ interpolation
Continuation of parallel operation with interpolated values
(only possible with circulating reactive current parallel oper-
ation method)
Power factor
Circulating reactive current minimization without CAN bus
communication parallel operation method
Table 44: Behavior if no communication present
9.3.3.2.11 Setting delay time for parallel operation error messages
You can use this parameter to set the delay time for a parallel operation er-
ror message so that brief fault messages are not received if the motor-drive
units involved in the parallel operation have different runtimes.
9.3.3.3 Parallel operation
In the parallel operation menu, you can display information about the de-
vices that are connected by CAN bus.
Description
Parallel operation status:
▪ Gray = Independent mode
▪ Blue = Parallel operation is active
▪ Red = Parallel operation error
CAN addr.
CAN bus address
Grp.
Parallel operation group
Method
Active parallel operation method
Current tap position
U [V]
Voltage
I_p [%]
Active current
I_q [%]
Reactive current
Blocking:
▪ Gray: Parallel operation not blocked
▪ Red: Parallel operation blocked
Table 45: Information about parallel operation
► Go to
Information > Parallel operation
.