Operation
59
5.9 Advanced Menu (continued)
Menu
Description
Min
Max
Default Unit
Reg. Type
PNU 28800
Advanced
Stop Settings
Stop Current Limit
Stop Current Limit
Level
The current in Amps at which
the soft stop ramp is not
allowed to go above.
Normally set to 350% motor
FLC. Increase if motor
decelerates too rapidly.
The current limit level will
affect actual time to stop the
motor.
100% I-
motor
450% I-
unit
350% I-
motor
A
Read/Write
PNU 28864
Advanced
Stop Settings
Stop Current Limit
Stop Current Limit
Time
The maximum time allowed for
the current limit.
If the current limit is still active
at the end of this period, the
Unit will either trip or continue.
1
300
10
s
Read/Write
PNU 25728
Advanced
Motor Protection
↓
Motor Current
This should be set to the Full
Load Current shown on the
motor plate.
The overload works with
multiples of the set "Motor
Current" (i-motor).
Also referred to as Motor FLA
(I-motor).
10%
I-unit
100%
I-rated
100%
I-rated
A
Read/Write
PNU 25664
Advanced
Motor Protection
↓
Trip Class
The trip class is a numeric
value that correlates the trip
time with overload level.
Select Trip class according to
application requirements.
The trip time depends on the
selected Trip Class. The
duration of the overload and
the level of the over current.
Refer to the Motor Overload
'cold' trip curves given in the
Quick Start Guide.
When "Class 20" or "Class 30"
are selected the Unit current
rating (i-Unit) will be reduced
to a lower value (i-rated).
Trip
Class
10
Trip
Class 30
Trip
Class 10
Read/Write