Operation
56
5.9 Advanced Menu (continued)
Menu
Description
Min
Max
Default Unit Reg. Type
PNU 19904
Advanced
Automatic Settings
↓
Automatic End Start (2)
Automatically controls the time
taken for the motor to start
On : The ramp time is
shortened if torque fluctuations
occur before the end of the
"Start Time"
Off: The ramp time depends on
the "Start Time" and "Current
Limit"
Off
On
Off
Read/Write
PNU 20032
Advanced
Automatic Settings
↓
Automatic End Start (3)
Automatically controls the time
taken for the motor to start
On : The ramp time is
shortened if torque fluctuations
occur before the end of the
"Start Time"
Off: The ramp time depends on
the "Start Time" and "Current
Limit"
Off
On
Off
Read/Write
PNU 768
Advanced
Automatic Settings
↓
Rate End Start (3)
Adjusts the response of the
"Automatic End Start (3)"
Increase to provide a greater
smoothing effect If there are
torque fluctuations that occur
during the soft start.
When set to zero the smoothing
is effectively disabled.
0
100
%
Read/Write
PNU 7104
Advanced
Start Settings
↓
Start Time
Time taken to soft start from
the "Start Pedestal" to the end
of the start
Normally set between 5 and
30 seconds. Actual time to get
to full voltage depends on the
"Start Current Limit Level".
If set too long the motor can
be at speed before the end of
the time set. Refer to
"Automatic End Start"
1
300
10
s
Read/Write
PNU 704
Advanced
Start Settings
↓
Start Pedestal
Percentage of the supply
voltage applied to motor at the
beginning of the soft start.
Increase to provide more
torque If the load fails to break
away.
Decrease if the motor
accelerates too quickly.
10
100
20
%