![motortronics VMX-Synergy Plus User Manual Download Page 21](http://html1.mh-extra.com/html/motortronics/vmx-synergy-plus/vmx-synergy-plus_user-manual_1839367021.webp)
Installation
21
4. Ratings and Technical Information
4.1 Rating Table
Minimum current ratings based on typical rated operation currents of motors for the corresponding
rated operational powers.
Current rating optimised for kW@500V & HP@550-600V - Ref IEC 60947-4-1 Table G.1 where
applicable.
Size 1,2 and 3
Type
I
e
kW
1)
FLA
HP
2)
U
s
A
3)
230V 400V 500V A
3)
200V 208V 220-240V 440-480V 550-600V
VMX-SGY-I-17-6-01
17
4
7.5
7.5
17
3
5
5
10
15
VMX-SGY-I-22-6-01
22
5.5
11
11
22
5
5
5
15
20
VMX-SGY-I-29-6-01
29
7.5
15
15
27
7.5
7.5
7.5
20
25
VMX-SGY-I-35-6-01
35
7.5 18.5 22
34
10
10
10
25
30
VMX-SGY-I-41-6-01
41
11
22
22
41
10
10
10
30
40
24VDC,
VMX-SGY-I-55-6-01
55
15
30
37
52
15
15
15
40
50
110VAC
VMX-SGY-I-66-6-01
66
18.5 37
45
65
20
20
20
50
60
to
VMX-SGY-I-80-6-01
80
22
45
55
77
20
25
25
60
75
230VAC
VMX-SGY-I-100-6-01 100
30
55
55
99
30
30
30
75
100
VMX-SGY-I-132-6-01 132
37
75
90
125
40
40
40
100
125
VMX-SGY-I-160-6-01 160
45
90
110 156
50
50
60
125
150
VMX-SGY-I-195-6-01 195
55
110 132 192
60
60
75
150
200
VMX-SGY-I-242-6-01 242
75
132 160 242
75
75
75
200
250
VMX-SGY-I-302-6-01 302
90
160 200 302
100
100
100
250
300
VMX-SGY-I-361-6-01 361
110 200 250 361
125
125
150
300
350
VMX-SGY-I-430-6-02 430
132 250 250 414
150
150
150
350
450
110VAC
VMX-SGY-I-500-6-02 500
150 280 355 477
150
150
150
400
500
VMX-SGY-I-430-6-03 430
132 250 250 414
150
150
150
350
450
230VAC
VMX-SGY-I-500-6-03 500
150 280 355 480
150
150
200
400
500
1)
Rated operational powers in kW as per IEC 60072-1 (primary series) corresponding to IEC current rating.
2)
Rated operational powers in HP corresponding to FLA current rating according to UL508 and Table
430.250 of the National Electrical Code.
3)
The Ie and FLA rating applies for a maximum surrounding air temperature of 50
o
C. Above 50
o
C de-rate
linearly by 4% of Ie or FLA per
o
C to a maximum of 60
o
C.