Operation
53
5.8 Auto Setup Menu (continued)
Menu
Description
Min
Max
Default Unit Reg. Type
PNU 59392
Auto Setup
↓
↓
Control Method
Local Touch Screen : Control
using the buttons on the keypad.
User Programmable : Control
using the terminals. Function
defined in "I/O" menu.
Two Wire Control : Control using
terminals. Functions fixed as
shown on screen.
Three Wire Control : Control
using terminals. Functions fixed
as shown on screen.
Modbus Network : Control via
remote Modbus network or
Modbus TCP
Local
Touch
Screen
Modbus
Local
Touch
Screen
Read/Write
PNU 10880
Auto Setup
↓
↓
Digital Input Voltage
The digital inputs D1-1I D1-2I
D2-1I D2-2I are designed to
work with a range of control
supplies
230V : 'Active high level' Input
voltage must be in the range
195.5V - 253V
110V : 'Active high level' Input
voltage must be in the range
93.5V - 132V
24V : 'Active high level ' input
voltage must be in the range
20.4V-26.4V
It is important to
ensure the "Digital input
Voltage" corresponds to
the voltage applied to
the input. Failure to do
so may result in
damage
230V
24Vdc
230V
Read/Write