Operation
65
5.9 Advanced Menu (continued)
Menu
Description
Min
Max
Default
Unit Reg. Type
PNU 53787
Advanced
Trip Settings
↓
Low Current Trip
This can be used to detect if
the motor is running lightly
loaded.
On: The Unit will trip. This
feature is not active during soft
start and soft stop.
Off: The Unit will continue to
operate regardless of motor
current.
Off
On
Off
Read/Write
PNU 53790
Advanced
Trip Settings
↓
Start Current Limit Trip
Selects trip or continue if the
current limit has been active
for too long.
On: The Unit will trip.
Off: The start will continue
regardless of the motor current
level.
Off
On
On
Read/Write
PNU 53791
Advanced
Trip Settings
↓
Stop Current Limit Trip
Selects trip or continue if the
stop current limit has been
active for too long.
On: The Unit will trip.
Off: The stop will continue
regardless of the motor current
level.
Off
On
Off
Read/Write
PNU 53794
Advanced
Trip Settings
↓
PTC Motor Thermistor
Trip
A single PTC motor thermistor
or set of PTC motor
thermistors can be connected
to the PTC terminals.
On: The Unit will trip if the
motor thermistor exceeds its
response temperature or the
PTC input is open circuit.
Off: The unit will not trip
regardless of motor rotation.
Off
On
Off
Read/Write
PNU 53808
Advanced
Trip Settings
↓
L1-L2-L3 Trip
Determines if supply phase
sequence is incorrect for motor
rotation.
On: Trips if the phase
sequence is L1-L2-L3.
Off: The unit will not trip
regardless of motor rotation.
Off
On
Off
Read/Write