Operation
86
5.11 Monitor Menu (continued)
PNU 33024
Monitor
↓
↓
True Power Factor
The True Power Factor =
(Displacement Power Factor x
Distortion Power Factor )
0
1
0
Read Only
PNU 34688
Monitor
↓
↓
True Power P
Total true power (Estimated).
This is an addition of the 3
phases.
0
10000
0
kW
Read Only
PNU 34816
Monitor
↓
↓
Apparent Power S
Total Apparent Power
This is an addition of the 3
phases.
0
10000
0
kVA
Read Only
PNU 34944
Monitor
↓
↓
Reactive Power Q
Total Reactive Power
This is an addition of the 3
phases.
0
10000
0
kvar
Read Only
PNU 35008
Monitor
↓
↓
iERS Saving Level
Indicates the level of potential
saving.
100% indicates that Unit is
saving at its maximum level.
Does not indicated real
percentage saving.
0
100
0
%
Read Only
PNU 22400
Monitor
↓
↓
Delay Angle
Internal firing delay angle in
Degrees.
Displayed for diagnostic
purposes.
0
60
0
Deg
Read Only