Installation
18
3.4.2 User Programmable Control
110/230Vac (US) and (UC) user programmable
24Vdc (US) and (UC) user programmable
control diagram
control diagram (VMX-SGY-I-17 to VMX-SGY-I-361)
L
N
D1-1I
D1COM
D1-2I
D2COM
D2-1I
53
54
FU1
110/230VAC
N
LINE ISOLATION
CONTACTOR
K2
K2
RESET
STOP
START
(OPTIONAL)
EMERGENCY STOP
K1
K2
24VDC
0VDC
D1-1I
D1COM
D1-2I
D2COM
D2-1I
53
54
FU1
24VDC
0V
LINE ISOLATION
CONTACTOR
RESET
K2
STOP
START
(OPTIONAL)
EMERGENCY STOP
K1
K2
K2
User programmable inputs are full programmable
1) Optional high reset. If this reset is required ensure “User
Programmable” is selected in the control method menu found
in the Digital Inputs menu. If you would prefer the reset to work
by removing and reapplying the Start Signal on D1 - 1I then
select “Two wire control” in the control method menu.
D1 – 1I = High Start / Low Stop
D1 – 2I = None
D2 – 1I = High Reset