Operation
47
5.7.2 ‘Input/Output’ (I/O) Category (continued)
Group
Parameter
Units Range
Read/
Write
Modbus
Default
Setting
User
Setting
Dec
Hex
Digital
Outputs
(continued)
Digital Output 4 N/O
(44) →
Select Function
(DO4)
–
same as DO1 function
selections
R/W 11587 2D43 End Of
Start
Digital Output 4 N/O (44) →
High Output =1 if On
N/A
OFF/ON
R/W 11910 2E86
ON
Digital Output 5 N/O (54) →
Select Function
(DO5)
–
same as DO1 function
selections
R/W 11588 2D44 Running
Digital Output 5 N/O (54) →
High Output =1 if On
N/A
OFF/ON
R/W 11912 2E88
ON
Analog
Inputs
Analog Input Type
N/A
0–10V/4–20mA
R/W 9600 2580 0–10V
Select Function
–
Off
Current Limit Start
Current Shearpin
Current Overload
R/W 9664 25C0 OFF
Scaling Level
–
Dependent on selected
function
R/W
9728
2600
16,384
Analog
Outputs
Analog Output Type
N/A 0–10V/4–20mA
R/W 8960 2300 0–10V
Select Function
–
Off
I Measured
Overload
P-Total
R/W 9024 2340 OFF
Scaling Level
–
Dependent on selected
function
R/W 9088 2380
0
PTC Motor Thermistor Trip
-
OFF/ON
R/W 53794 D222 OFF