Operation
91
5.11 Monitor Menu (continued)
Menu
Description
Min
Max
Default Unit Reg. Type
PNU 33409
Monitor
↓
Dynamic Reset
Dynamically tracks the thermal
capacity needed for a
successful restart after an
overload trip. It averages the
thermal capacity consumed in
the previous three successful
starts and calculates a thermal
capacity to start.
The calculated thermal
capacity is stored in the
“Dynamic Reset” register. After
tripping on overload, the
thermal “Overload” register
must have regained the
amount recorded in “Dynamic
Reset” before a reset will be
allowed.
If there is insufficient capacity
to start the unit it will be
inhibited from starting. The unit
can be reset when there is
sufficient capacity to start and
the start stop signal is not
present.
0
100
0
%
Read Only