Operation
46
5.7.2 ‘Input/Output’ (I/O) Category
Group
Parameter
Units Range
Read
/
Write
Modbus
Default Setting
User
Setting
Dec
Hex
Digital
Inputs
Digital Input Voltage
V
230Vac,110Vac or
24Vdc
R/W 10880 2A80
230Vac
Control Method
–
Local Touch Screen
User Programmable
Two Wire Control
Three Wire Control
Modbus
R/W 59392 E800
Local Touch
Screen
Digital Input 1 (D1-
1I) →
Select Function
–
Off
Start/Stop
Freeze Ramp
Reset
iERS
External Trip
R/W 10944 2AC0
Start/ Stop
Digital Input 1 (D1-
1I) →
High Input =1 if On
N/A OFF/ON
R/W 11264 2C00
ON
Digital Input 2 (D1-
2I) →
Select Function
–
same as DI-1I
function selections
R/W 10945 2AC1
OFF
Digital Input 2 (D1-
2I) →
High Input =1 if On
N/A OFF/ON
R/W 11266 2C02
ON
Digital Input 3 (D2-
1I) →
Select Function
–
same as DI-1I function
selections
R/W 10946 2AC2
Reset
Digital Input 3 (D2-
1I) →
High Input =1 if On
N/A OFF/ON
R/W 11268 2C04
ON
Digital Input 4 (D2-
2I) →
Select Function
–
same as DI-1I function
selections
R/W 10947 2AC3
OFF
Digital Input 4 (D2-
2I) →
High Input =1 if On
N/A OFF/ON
R/W 11270 2C06
ON
Digital
Outputs
Digital Output 1 N/C (12) →
Select Function
(DO1)
–
Off
Ready
Enabled
Error
Running
End of Start
Current Limit
iERS Active
Auto Reset Pending
Auto Reset Exceeded
Shearpin
Low Current
R/W 11584 2D40
Error
Digital Output 1 N/C (12) →
High Output =1 if On
N/A OFF/ON
R/W 11904 2E80
ON
Digital Output 2 N/O (24) →
Select Function
(DO2)
–
same as DO1
function
selections
R/W 11585 2D41
Error
Digital Output 2 N/O (24) →
High Output =1 if On
N/A OFF/ON
R/W 11906 2E82
ON
Digital Output 3 N/O (34) →
Select Function
(DO3)
–
same as DO1
function
selections
R/W 11586 2D42
Running
Digital Output 3 N/O (34) →
High Output =1 if On
N/A OFF/ON
R/W 11908 2E84
ON