Operation
63
5.9 Advanced Menu (continued)
Menu
Description
Min
Max
Default
Unit Reg. Type
PNU 21376
Advanced
iERS
↓
iERS Level
Determines the maximum
energy saving potential.
Reduce if the application
shows signs of instability.
The amount of energy that can
be saved may fall as the "iERS
level" is reduced.
0
100
100
%
Read/Write
PNU 35200
Advanced
iERS
↓
Fixed Voltage
User settable voltage level for
power calculations
If a very high level of accuracy
is required the user can input
the 3-Phase voltage directly
100
500
100
V
Read/Write
PNU 35264
Advanced
iERS
↓
Fixed Voltage
Selects the source for the
voltage value used in the
power calculations.
on: KW KVar and KVA are
calculated using the "Fixed
Voltage".
off: KW KVar and KVA are
calculated using the internally
measured voltage.
Off
On
Off
Read/Write
PNU 59392
Advanced
↓
↓
Control Method
Local Touch Screen : Control
using the buttons on the
keypad.
User Programmable : Control
using the terminals. Function
defined in "I/O" menu.
Two Wire Control : Control
using terminals. Functions
fixed as shown on screen.
Three Wire Control : Control
using terminals. Functions
fixed as shown on screen.
Modbus Network : Control via
remote Modbus network or
Modbus TCP
Local
Touch
Screen
Modbus
Network
Local
Touch
Screen
Read/Write