![motortronics VMX-Synergy Plus User Manual Download Page 115](http://html1.mh-extra.com/html/motortronics/vmx-synergy-plus/vmx-synergy-plus_user-manual_1839367115.webp)
Operation
115
5.14 Functional Summaries
5.14.1 Automatic Settings
Automatic Pedestal
- Automatic overriding of the start pedestal. When On the unit approximately detects
the start of motor rotation and tries to adjust the pedestal to suit..
Automatic End Start
- Automatic detection of motor full speed during the start-up. Having detected motor
full speed achieved before the end of the programmed ramp, this menu item brings forward the end of the
ramp cutting short an overlong programmed start.
Automatic Ramp
- Automatically detects motor acceleration and dynamically adjusts the ramp to give
smoother acceleration. This menu item works in conjunction with the Start Time parameter which should be
set to the estimated start time of the load. This would be suitable for starts with varying loads.
Automatic Stop
- Automatic adjustment of the soft stop. When On the unit attempts to automatically adjust
the soft stop profile to suit the load.
Automatic End Stop
- Automatic detection of a stalled motor during soft stop. When On and the motor has
stopped before the end of the unit’s programmed soft stop the unit will attempt to detect the stall and turn
off the thyristors thus truncating the soft stop time.
Auto End Stop
- Automatic detection of a stalled motor during soft stop. When On and the motor has
stopped before the end of the unit’s programmed soft stop the unit will attempt to detect the stall and turn
off the thyristors thus truncating the soft stop time.