Operation
49
5.7.4 ‘Log’ Category
Group
Parameter
Units Range
Read/
Write
Modbus
Default
Setting
User
Setting
Dec Hex
Trip Log
Last Trip
–
0 to 65,535
Read 60608 ECC0
0
–
Last Trip -1
–
0 to 65,535
Read 60609 ECC1
0
–
Last Trip -2
–
0 to 65,535
Read 60610 ECC2
0
–
Last Trip -3
–
0 to 65,535
Read 60611 ECC3
0
–
Last Trip -4
–
0 to 65,535
Read 60612 ECC4
0
–
Last Trip -5
–
0 to 65,535
Read 60613 ECC5
0
–
Last Trip -6
–
0 to 65,535
Read 60614 ECC6
0
–
Last Trip -7
–
0 to 65,535
Read 60615 ECC7
0
–
Last Trip -8
–
0 to 65,535
Read 60616 ECC8
0
–
Last Trip -9
–
0 to 65,535
Read 60617 ECC9
0
–
Start Current
Log
Last Peak Start Current
A
0 to 10,000
Read 38400 9600
0
–
Last Peak Start Current -1
A
0 to 10,000
Read 38402 9602
0
–
Last Peak Start Current -2
A
0 to 10,000
Read 38404 9604
0
–
Last Peak Start Current -3
A
0 to 10,000
Read 38406 9606
0
–
Last Peak Start Current -4
A
0 to 10,000
Read 38408 9608
0
–
Last Peak Start Current -5
A
0 to 10,000
Read 38410 960A
0
–
Last Peak Start Current -6
A
0 to 10,000
Read 38412 960C
0
–
Last Peak Start Current -7
A
0 to 10,000
Read 38414 960E
0
–
Last Peak Start Current -8
A
0 to 10,000
Read 38416 9610
0
–
Last Peak Start Current -9
A
0 to 10,000
Read 38418 9610
0
–