Operation
45
5.7.1 ‘Advanced’ Category (continued)
Group
Parameter
Units
Range
Read/
Write
Modbus
Default
Setting
User
Setting
Dec
Hex
Auto Reset
Auto Reset
N/A
OFF/ON
R/W
20736 5100
Off
Reset Delay
s
0 to 7200
R/W
20737 5101
0
Reset Attempts
N/A
0 to 10
R/W
20738 5102
0
Trip Free Time
s
0 to 7200
R/W
20739 5103
600
Input Side Phase Loss
N/A
OFF/ON
R/W
20801 5141
ON
Motor Side Phase Loss
N/A
OFF/ON
R/W
20804 5144
ON
Overload
N/A
OFF/ON
R/W
20813 514D
ON
Thyristor Firing
N/A
OFF/ON
R/W
20803 5143
ON
Sensing Fault
N/A
OFF/ON
R/W
20807 5147
ON
Thermal
N/A
OFF/ON
R/W
20802 5142
ON
Low Current
N/A
OFF/ON
R/W
20811 514B
ON
Current Limit time Out
N/A
OFF/ON
R/W
20812 514C
ON
Shearpin
N/A
OFF/ON
R/W
20814 514E
ON
Current Sensor
N/A
OFF/ON
R/W
20823 5157
ON
Control Voltage Low
N/A
OFF/ON
R/W
20806 5146
ON
Fan
N/A
OFF/ON
R/W
20808 5148
ON
External
N/A
OFF/ON
R/W
20816 5150
ON
Communications
N/A
OFF/ON
R/W
20817 5151
ON
Bypass
N/A
OFF/ON
R/W
20818 5152
ON
PTC Thermistor
N/A
OFF/ON
R/W
20815 514F
OFF
Phase Rotation
N/A
OFF/ON
R/W
20821 5155
OFF
Operation 1
N/A
OFF/ON
R/W
20826 515A
ON
Operation 2
N/A
OFF/ON
R/W
20822 5156
ON
Operation 4
N/A
OFF/ON
R/W
20826 515A
ON
Operation 5
N/A
OFF/ON
R/W
20824 5158
ON