Operation
69
5.9 Advanced Menu (continued)
Menu
Description
Min
Max
Default Unit Reg. Type
PNU 53768
Advanced
Trip Settings
↓
Thermal Sensor Trip
Detects if the internal
temperature sensor has
malfunctioned.
On: The Unit will trip if the
internal temperature sensor
malfunctions.
Off: The Unit will continue to
operate even if the
temperature sensor has
malfunctioned.
Operating in this mode for
prolonged periods may result
in SCR failure.
Off
On
On
Read/Write
PNU 53795
Advanced
Trip Settings
↓
External Trip
Allows a trip to be forced using
one of the digital inputs.
On: Trips when the
programmed input is active.
Off: External Trip is disabled.
Off
On
On
Read/Write
PNU 53799
Advanced
Trip Settings
↓
Operation 1 Trip
Detects if the logging function
has failed to operate normally.
On : Operation 1 trip enabled.
(Trip Code 2601-2699)
Off: Operation 1 trip disabled.
Off
On
Off
Read/Write
PNU 53800
Advanced
Trip Settings
↓
Operation 2 Trip
Detects if the Control Board
has failed to operate normally.
On : Operation 2 trip enabled.
(Trip Code 2401-2499)
Off: Operation 2 trip disabled.
Off
On
On
Read/Write