Operation
85
5.11 Monitor Menu (continued)
Menu
Description
Min
Max
Default
Unit
Reg. Type
PNU 33920
Monitor
↓
↓
V1
The voltage on phase L1
0
1000
0
V
Read Only
PNU 33921
Monitor
↓
↓
V2
The voltage on phase L2
0
1000
0
V
Read Only
PNU 33922
Monitor
↓
↓
V3
The voltage on phase L3
0
1000
0
V
Read Only
PNU 32960
Monitor
↓
↓
Voltage Vrms
The RMS 3-phase supply
voltage.
This is the average of the 3
phases. This value is used for
power calculations.
This value is derived internally.
If a higher level of accuracy is
required a "Fixed Voltage" value
can be used.
0
1000
0
V
Read Only
PNU 36544
Monitor
↓
↓
HeatSink Temp
The temperature of the internal
Unit heatsink.
The Unit will trip when the
heatsink temperature exceeds
90°C.
The internal cooling fans will
turn on if this temperature
exceeds 40°C.
-20
90
0
°C or °F Read Only