5.12 Log Menu (continued)
Menu
Description
Min
Max
Default Unit Reg. Type
PNU -
Log
Trip Log
Trip Code Descriptions
2001-2003
Remote Start is
Enabled
The remote start signal is
active.
The remote start signal was
active during power up or
Reset or Parameter Load.
Turn off remote or if Remote
On trip is not required turn "off"
in "Trip Settings".
Read Only
PNU -
Log
Trip Log
Trip Code Descriptions
2101
Rotation L1 L2 L3 Trip
The input phase rotation is
RYB (L1-L2-L3).
The phase rotation is opposite
to that required.
Change phase rotation or if
"RYB" trip is not required turn
"off" in trip settings.
Read Only
PNU -
Log
Trip Log
Trip Code Descriptions
2102
Rotation L1 L3 L2 Trip
The input phase rotation is
RBY (L1-L3-L2).
The phase rotation is opposite
to that required.
Change phase rotation or if
"RBY" trip is not required turn
"off" in trip settings.
Read Only
PNU -
Log
Trip Log
Trip Code Descriptions
2201-2299
MPU Trip
Internal Unit Failure.
The Unit has failed internally
and is unable to recover
automatically.
Cycle the control supply.
If the fault is not cleared, then
contact the supplier.
Read Only
PNU -
Log
Trip Log
Trip Code Descriptions
2301-2303
Current Sensor Trip
Current sensor failure.
One or more of the internal
sensors used to measure
current has failed or is reading
a low value.
Check the connections to the
supply and motor as
disconnection will result in a
zero current reading.
Check the plate FLA of the
motor being controlled is at
least 25% of the "i-motor"
rating.
Read Only