Troubleshooting Reference
2-61
element
TM
Series
Door Bypass Inspection (126)
Machine Room inspection is active and one or both of the Car/Hoistway
Door Bypass switches is in the Bypass position. Cannot be bypassed.
System Verifies:
- ModeofOperation = OpModeInspectionBP
Correction:
1. Turn off one or both of the Car/Hoistway Door Bypass switches.
Door Close Fail 1 (77)
Door Close Fail 2 (78)
Door Close Fail 3 (79)
Door Close Fail 4 (80)
Detected for each failed attempt to close the doors at a destination floor.
Cleared if the doors successfully close. Cannot be bypassed.
System Verifies:
- Door Flags, Door Command Data, Door Close Fail = 1 (2, 3, 4)
Correction:
1. Check all door contacts.
2. Check for correct door operation and speed.
3. Check fuses FDLN1 and FDLN2.
Door Close Fault (15)
Doors have tried and failed to close three times. (See Door Close Fail 1 -
3.) All calls are canceled. Cleared when doors successfully close or by
pressing fault reset button. Also cleared by cycling controller power or if
mode of operation is changed. Fault bypassed in Construction/Inspection.
System Verifies:
- Door close fault flag
Correction:
1. Check all door contacts.
2. Check fuses FDLN1, FDLN2.
3. Check for correct door operation and speed.
Door Fault Shutdown (108)
The door has failed to close after three closing cycles have been
attempted. Doors will fully open and car will shut down. Fault bypassed in
Construction/Inspection.
Door Hold (110)
The Door Hold input is active. Fault bypassed in Construction/Inspection.
System Verifies:
- Door Flags, Door Hold Data, Door Hold Function active.
Correction:
1. If in error, check wiring (be sure that door hold timer has expired).
Door Open Fail 1 (73)
Door Open Fail 2 (74)
Door Open Fail 3 (75)
Door Open Fail 4 (76)
Detected for each failed attempt to open the doors at a destination floor.
Cleared if the doors successfully open. Cannot be bypassed.
System Verifies:
- Door Flags, Door Command Data, Door Open Fail = 1 (2, 3, 4)
Correction:
1. Check all door contacts.
2. Check the user defined Open Time Limit.
3. Check for correct door operation and speed.
4. Check fuses FDLN1, FDLN2.
Door Open Fault (13)
Doors have tried and failed to open three times. (See Door Open Fail 1 -
3.) All calls are canceled. Door may be opened with constant pressure on
door open button. Cleared when doors successfully open or by pressing
fault reset button. Also cleared by cycling controller power or if mode of
operation is changed. Fault-bypassed in Construction/Inspection.
System Verifies:
- Door open fault flag
Correction:
1. Check all door contacts.
2. Check the user defined Open Time Limit.
3. Check for correct door operation and speed.
4. Check fuses FDLN1, FDLN2.
Table 2.15 Touch Screen Event Listings
Event
Description