Installation
1-8 Manual # 42-02-2P26
Construction Operation
Construction operation is for use when all hoistway equip-
ment may not yet be installed. On Construction operation, the car is moved using cartop or
machine room inspection inputs. To enter construction operation:
• The INSP/NORM switch on the CPU board must be in INSP position.
• The FLT BYPASS jumper just below the CPU board MACHINE RM INSPECTION switches
must be in the BYPASS position.
• On the Utils (Utilities) tab > Construct and Bypass Faults Menu, enable Construction
Fault Bypass.
To bypass door faults on Construction operation:
• Set the SCE-CPU board Car and Hoistway Door Bypass switches to BYPASS.
Attended Modes
Attended modes include Independent operation and fire service phase II operation.
Independent Service
When independent service is initiated, all existing car calls are
immediately canceled and the elevator is removed from hall call service. With the car stopped in
a door zone, if car doors are open, they will remain open; if closed, they will open. During inde-
pendent service the car is controlled by car calls.
Upon arriving at a call, the elevator doors open and will remain open until the attendant closes
the doors using constant pressure on the door close button or on a car call button. Hall and
jamb mounted arrival fixtures are inoperative.
Fire Service Phase II
When the car is placed on fire service phase II (in-car fire-
fighter) operation, the elevator will operate according to the applicable local fire code. For
example, A17.1 code:
• Constant pressure on the door close button initiates door closing.
• Registration of a destination call and pressing door close button initiates door closing.
• When exiting Fire Phase II and the car arrives at the fire recall floor, doors open automati-
cally.
Automatic Modes of Operation
Automatic modes include passenger mode, capture for test (pretest), and test modes.
Passenger Mode
During passenger mode, the car responds to hall and car calls under
selective-collective operation. Passenger mode is the default mode of operation and is active so
long as no other mode is selected.
Capture for Test (Pretest)
When placed in Pretest mode, the car is taken out of hall
call service and arrival annunciators disabled. Remaining car calls will be served and new car
calls may be placed but, when the car completes servicing car calls, it will recall to the desig-
nated Capture floor or remain at the last floor served; door action as programmed.
Capture operation is overridden by all modes except passenger operation.