Configuration and Troubleshooting
2-68 Manual # 42-02-2P26
Excessive Faults (129)
Generated when there are more than ten faults that resulted in an emer-
gency, controlled or ASAP stop. The counter resets if the car makes ten
normal runs without faults. The car is taken out of service and all regis-
tered calls are canceled. The car will proceed to the next available floor
and cycle the doors to let the passengers out. Once at a floor, the “Exces-
sive Faults Shutdown” fault is activated and the car will remain shut down
until the Fault Reset button is pressed, Inspection is toggled or power to
the controller is cycled. Fault-bypassed in Construction/Inspection.
Correction:
1. Access the event log and determine which recent events triggered the
fault.
2. Troubleshoot those faults to prevent their recurrence.
Fire Bypassed (120)
Detected when fire service is activated but car cannot perform fire recall
due to certain conditions (Inspection, Test, or Independent Service mode
active). Cleared as soon as conditions preventing fire recall are cleared.
Cannot be bypassed.
Correction:
1. Check the current mode of operation and verify that the operation is
per the selected user defined fire code.
Fire II (25)
Fire Phase II, in-car firefighter operation, is active. Cannot be bypassed.
System Verifies:
- Mode of Operation = Fire II
Correction:
1. If in error, verify in-car fire fighter switch mechanically and electrically.
2. Verify status of System IO > Programmed Inputs > FR2 ON.
3. Verify FR2 ON input is not shorted.
Fire II Hold (17)
In-car fire fighter switch is in HOLD position. Cannot be bypassed.
System Verifies:
- Mode of Operation = Op Mode Fire II
- Fire Data = FIRE II HOLD
Correction:
1. If in error, verify in-car fire switch mechanically and electrically.
2. Verify correct wiring per job prints.
3. Verify status of FR2 HOLD flag at System IO > Programmed Inputs.
Fire II Recall (26)
The doors are closed, the in-car fire switch is off and the car is recalling
to the recall floor. Cannot be bypassed.
System Verifies:
- Mode of Operation = Fire Recall
Correction:
1. If in error, verify programmed Input System IO > Programmed Inputs
> FR2 ON.
Fire Recall Alt (28)
The car is recalling to the alternate fire recall floor. At the floor, the car
will behave as configured. Cannot be bypassed.
System Verifies:
- Mode of Operation = Fire Recall Alt
Correction:
1. If in error, verify operation of fire/smoke sensors on main recall floor.
2. Verify sensors wired according to job prints.
3. Verify System IO > System Input > FRA = on for normal.
Fire Recall Done (54)
The car has completed recall to the designated floor. Cannot be
bypassed.
System Verifies:
- Fire Data = Recall Complete
Table 2.15 Touch Screen Event Listings
Event
Description