7 FUNCTIONS
7.2 SIO Mode Function
SIO output function
The ON/OFF status (Y signal) of outputs is controlled with Remote output (RY) of the CC-Link IE Field Network.
To operate the SIO mode for outputs, turn on Channel n (CQ/Q) I/O switching command (RY10 to RY1F) in the initial
processing.
To apply the I/O switching setting changed in processing other than the initial processing and parameter setting on an
engineering tool, turn on Operation condition setting request flag (RWw0.b9).
Setting procedure
1.
Open the "CC IE Field Configuration" window.
For the master/local module RJ71GF11-T2
[Navigation window]
[Parameter]
[Module Information]
[RJ71GF11-T2]
[Module Parameter]
[Basic Settings]
[Network Configuration Settings]
2.
Open the "Parameter Processing of Slave Station" window.
From the list of stations, select an IO-Link module
[CC IE Field Configuration]
[Online]
[Parameter Processing of
Slave Station].
3.
Set "Method selection" to "Parameter Write".
4.
For each channel, set "Write Value" of "Pin configuration setting" to "OUTPUT".
Summary of Contents for CC-Link IE Field NZ2GF12A-60IOLH8
Page 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Page 2: ......
Page 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Page 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Page 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Page 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Page 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Page 157: ...I 155 MEMO ...
Page 161: ......