5 INSTALLATION AND WIRING
5.3 Wiring the Power Cable
37
5
5.3
Wiring the Power Cable
When wiring the power supply, wire the POWER IN terminal and the power supply connector of the IO-Link module.
While ensuring that the direction of the power cable connector is correct, insert it into the IO-Link module, and tighten the
power cable screw.
• Attach waterproof caps to connector not used.
• The product specifications are satisfied only when all of waterproof plugs are installed with the
recommended connectable devices and all screws are tightened with an appropriate torque. (
Recommended Connectable Device List)
Transition wiring of the power supply
When installing multiple IO-Link modules, the power can be supplied to the modules through transition wiring.
For transition wiring, connect wires between the POWER OUT terminal of the IO-Link module that will be the power supplier
and the POWER IN terminal of another IO-Link module that will be a power supply destination.
*1 The largest current flows from the power supplier to the power supply connector of the first IO-Link module. Ensure that the current
capacity of the power supply connector (for module/sensor power actuator power supply) of the first IO-Link module does not
exceed 9.3A.
For transition wiring, check the current consumption of each of wired IO-Link modules.
For the current consumption of an IO-Link module, refer to the following.
Page 21 Performance Specifications
Tightening torque
When connecting the power cable, tighten the waterproof plug to the following torque.
(1) External power supply
Screw type
Tightening torque
Power supply connector (7/8")
1.50N
m
*1
(1)
Summary of Contents for CC-Link IE Field NZ2GF12A-60IOLH8
Page 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Page 2: ......
Page 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Page 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Page 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Page 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Page 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Page 157: ...I 155 MEMO ...
Page 161: ......