2 SPECIFICATIONS
2.2 Performance Specifications
21
2
2.2
Performance Specifications
NZ2GF12A-60IOLH8 IO-Link module
Item
NZ2GF12A-60IOLH8
Module type
CC-Link IE Field Network
Intelligent device station
IO-Link
IO-Link master
Isolation method
Non-isolation
Protection degree
IP67
Wiring method for common
1 common
Surge suppressor
Zener diode
Fuse
Module: Not available
Channel: Available
Protection function
Overload protection
function
Overcurrent is detectable on the CQ, Q, and L+ terminals on each channel.
External interface
Module power supply part
7/8" waterproof connector, 5 pins, male/female
I/O part
M12 waterproof connector, 5 pins, female, A-code
Communication part
M12 waterproof connector, 8 pins, female, X-code
Channel setting
The following 3 modes are available.
• IO-Link mode
• SIO mode (digital input) (default)
• SIO mode (digital output)
IO-Link mode
Supported protocol
v1.12
Number of channels
8 channels max.
Max. load current (CQ)
500mA/channel, 9A/common
Max. load current (L+)
1.3A/channel, 9A/common
Transmission speed
• 4.8kbaud (COM1)
• 38.4kbaud (COM2)
• 230.4kbaud (COM3)
Determined by the IO-Link device connected.
SIO mode (CQ)
(digital input)
Number of points
8 points max.
Input type
Negative common (source type)
Rated input current
IEC 61131-2 Type3
Input resistance
IEC 61131-2 Type3
ON voltage/ON current
11VDC or more/15mA or more
OFF voltage/OFF current
5.0VDC or less/1.5mA or less
Input response time
(OFF
ON)
0.1ms or less (excluding the internal processing time)
Input response time
(ON
OFF)
0.1ms or less (excluding the internal processing time)
SIO mode (CQ)
(digital output)
Number of points
8 points max.
Output type
Source type
Max. load current
2A/point, 9A/common
Max. inrush current
17A (25
, 150
s or less)
Leakage current at OFF
5
A or less
Max. voltage drop at ON
0.85VDC, 2.0A
Output response time
(OFF
ON)
80
s or less
Output response time
(ON
OFF)
150
s or less
Summary of Contents for CC-Link IE Field NZ2GF12A-60IOLH8
Page 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Page 2: ......
Page 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Page 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Page 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Page 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Page 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Page 157: ...I 155 MEMO ...
Page 161: ......