128
11 TROUBLESHOOTING
11.6 List of Error Codes and the Warning Codes
Error Code List (Communication Error)
Error code
(hexadecimal)
Classification
Error definition and cause
Action
E106H
Communication
error
Incorrect data was requested in transient transmission.
Check the data of the RIWT instruction.
E107H
Communication
error
The IO-Link request failed.
E108H
Communication
error
The IO-Link setting data is incorrect.
E109H
Communication
error
The attribute code of transient transmission is incorrect.
Correct the attribute code using the RIWT instruction,
and retry the operation.
E110H
Communication
error
E112H
Communication
error
E113H
Communication
error
The number of data to read/write in transient
transmission is incorrect.
Correct the read address and write address using the
RIWT instruction, and retry the operation.
E114H
Communication
error
The received transient data is incorrect.
Correct the number of data (frame length) using the
RIWT instruction, and retry the operation.
E115H
Communication
error
The access code of transient transmission is incorrect.
Correct the access code using the RIWT instruction,
and retry the operation.
E116H
Communication
error
The attribute code of transient transmission is incorrect.
Correct the attribute code using the RIRD instruction,
and retry the operation.
E118H
Communication
error
E119H
Communication
error
The number of data to read/write in transient
transmission is incorrect.
Correct the read address and write address using the
RIRD instruction, and retry the operation.
E120H
Communication
error
The received transient data is incorrect.
Correct the number of data (frame length) using the
RIRD instruction, and retry the operation.
E121H
Communication
error
The access code of transient transmission is incorrect.
Correct the access code using the RIRD instruction,
and retry the operation.
E123H
Communication
error
The requested data is incorrect.
Check the parameter of the RIRD instruction.
Summary of Contents for CC-Link IE Field NZ2GF12A-60IOLH8
Page 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Page 2: ......
Page 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Page 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Page 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Page 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Page 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Page 157: ...I 155 MEMO ...
Page 161: ......