7 FUNCTIONS
7.6 CC-Link IE Field Network Communication Function
83
7
Transient transmission
This function reads or writes data on the IO-Link module in line with a dedicated instruction from the master station.
The IO-Link module uses the RIRD instruction or RIWT instruction to perform transient transmission.
Data that can be read and written in transient transmission
The following table lists the IO-Link module data that can be read and written in transient transmission on the CC-Link IE Field
Network.
Specify the access code, attribute code, and address code via the control data of the RIRD instruction or RIWT instruction.
For details, refer to the following.
User's manual for the master/local module used
MELSEC iQ-R Programming Manual (Module Dedicated Instructions)
*1 The address code indicates the storage location of each data to be read or written.
Data name
Access
code
Attribute
code
Address
code
Description
Readable/Writable
Reference
IO-Link module
identification data
10H
05H
10H to 17H
Read IO-Link module identification
data.
Read
Page 84 IO-Link
module
identification data
Initial operation setting
11H
05H
00H
Enable/disable the initial processing
when starting the IO-Link module.
Read/Write
Page 84 Initial
operation setting
Output HOLD/CLEAR
setting
12H
05H
00H
Configure the HOLD/CLEAR setting
of the output value for cases where a
communication error occurs.
Read/Write
Page 85 Output
HOLD/CLEAR
setting
Number of ON times
13H
05H
00H to 07H
Read the output ON times (count) in
SIO mode.
Read/Write
Process data size
20H
05H
00H
Configure the swap setting and
process data size for each channel.
Read/Write
Device validation
21H
05H
00H to 07H
Validates compatibility and identity of
the IO-Link devices connected to the
IO-Link module.
Read/Write
Data storage configuration
22H
05H
00H
Configure the data storage setting for
each channel.
Read/Write
Page 88 Data
storage
configuration
Data storage content
24H
05H
00H to 07H
Read parameters in the data storage
of each channel.
Read
ISDU
30H
05H
00H to 07H
Read/write the IO-Link device
parameters.
Read/Write
Event data
31H
05H
00H to 07H
Read event data that has occurred on
the IO-Link devices.
Read
Summary of Contents for CC-Link IE Field NZ2GF12A-60IOLH8
Page 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Page 2: ......
Page 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Page 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Page 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Page 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Page 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Page 157: ...I 155 MEMO ...
Page 161: ......