88
7 FUNCTIONS
7.6 CC-Link IE Field Network Communication Function
■
Data storage configuration
Configure the data storage setting for each channel.
The data storage is the area in which the IO-Link device parameters are stored, and is used by the IO-Link device setting
automatic upload/download function.
The following table shows the data storage configuration and data configuration of each channel.
• Upload setting
• Download setting
• Data storage deletion request
• Data storage configuration
Enable the Data storage configuration when the Upload setting and Download setting are enabled. It is not
possible to enable only the Data storage configuration.
Disable the Data storage configuration when the Data storage deletion request is enabled.
Item
Description
Access code
22H
Attribute code
05H
Address code
00H
Data size
8 bytes
Data
• First byte: The data storage configuration of the IO-Link module channel 1 (Default: 00H)
• Second byte: The data storage configuration of the IO-Link module channel 2 (Default: 00H)
• Third byte: The data storage configuration of the IO-Link module channel 3 (Default: 00H)
• Fourth byte: The data storage configuration of the IO-Link module channel 4 (Default: 00H)
• Fifth byte: The data storage configuration of the IO-Link module channel 5 (Default: 00H)
• Sixth byte: The data storage configuration of the IO-Link module channel 6 (Default: 00H)
• Seventh byte: The data storage configuration of the IO-Link module channel 7 (Default: 00H)
• Eighth byte: The data storage configuration of the IO-Link module channel 8 (Default: 00H)
Data configuration
Description
b0
Upload setting (0: Disabled, 1: Enabled)
b1
Download setting (0: Disabled, 1: Enabled)
b2 to b5
Use prohibited (fixed to 0)
b6
Data storage deletion request (0: Not delete, 1: Delete)
b7
Data storage configuration (0: Disabled, 1: Enabled)
• Enabled: Parameters of each IO-Link device parameters are uploaded to the data storage of the IO-Link module.
• Disabled: Parameters of each IO-Link device are not uploaded. However, if there is no parameters in the data storage of the IO-Link module, the IO-Link
device parameters are uploaded.
• Enabled: Parameters in the data storage of the IO-Link module are downloaded to each IO-Link device.
• Disabled: Parameters in the data storage of the IO-Link module are not downloaded.
• Delete: Parameters saved in the data storage of the IO-Link module are deleted.
• Not delete: Parameters saved in the data storage of the IO-Link module are not deleted.
• Enabled: Parameters are saved in the data storage of the IO-Link module.
• Disabled: Parameters are not saved in the data storage of the IO-Link module. However, if parameters already exist in the data storage, the parameters are
not deleted even if this setting is disabled.
Summary of Contents for CC-Link IE Field NZ2GF12A-60IOLH8
Page 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Page 2: ......
Page 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Page 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Page 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Page 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Page 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Page 157: ...I 155 MEMO ...