6 Parameter Setting
6.4 IO-Link Device Parameter Setting
57
6
6.4
IO-Link Device Parameter Setting
Using CommDTM for IO-Link master module in FDT, IO-Link device parameters can be read or written and data can be
monitored via the IO-Link module. In addition, multiple IO-Link devices can be managed from one place. IODD can be
converted to Device DTM using IODD DTM Configurator. IODD is supplied from the sensor manufacturer.
Setting procedure when FDC and CommDTM are used
The following describes how to set the IO-Link device parameter.
Setting procedure
1.
Install IODD using the installer supplied from the manufacturer of the sensor. Convert IODD supplied from the sensor
manufacturer to Device DTM using IODD DTM Configurator. When Device DTM is supplied from the sensor
manufacturer, this operation is not necessary.
Page 59 Conversion procedure of IODD
2.
When GX Works3 is used, double-click the IO-Link module in the network map in GX Works3 after installing Device
DTM. When GX Works2 is used, start FDC directly.
3.
Register M_CommDTM-IOLink and Device DTM to the DTM catalog of FDC. This registration is necessary only for the
first startup. It will not be necessary for the next and subsequent startups.
Summary of Contents for CC-Link IE Field NZ2GF12A-60IOLH8
Page 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Page 2: ......
Page 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Page 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Page 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Page 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Page 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Page 157: ...I 155 MEMO ...
Page 161: ......