7 FUNCTIONS
7.3 Power Supply Monitoring Function
7.3
Power Supply Monitoring Function
This function checks the module/sensor power supply (US) voltage and the actuator power supply (UA) voltage, and notifies
of the status when voltage drops.
The module/sensor power supply voltage must be normal to check the actuator power supply voltage properly.
Description
If the module/sensor power supply voltage and actuator power supply voltage drop, the status can be checked with the
remote input signal (RX) and the LED indication.
For details on the remote input signal (RX), refer to the following.
Page 134 US voltage drop flag (18V or lower) (RX28)
Page 134 UA voltage drop flag (18V or lower) (RX29)
Page 134 UA voltage drop flag (11V or lower) (RX2A)
Setting procedure
This function is always enabled and parameter setting is not required.
Type
Detection condition
Remote input signal
LED indication
Module/sensor power supply (US)
18V or less
The US voltage drop flag (18V or
lower) (RX28) is ON.
The US LED is on in red.
Actuator power supply (UA)
18V or less
The UA voltage drop flag (18V or
lower) (RX29) is ON.
The UA LED flashes in red.
11V or less
The UA voltage drop flag (11V or
lower) (RX2A) is ON.
The UA LED is on in red.
Summary of Contents for CC-Link IE Field NZ2GF12A-60IOLH8
Page 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Page 2: ......
Page 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Page 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Page 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Page 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Page 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Page 157: ...I 155 MEMO ...
Page 161: ......