7 FUNCTIONS
7.6 CC-Link IE Field Network Communication Function
■
Number of ON times
Read the output ON times (count) in SIO mode.
To reset the integration value, write 0000H.
The output ON times integration value is reset to 0 to restart counting when it exceeds 65535.
For details on the output ON times integration value, refer to the following.
Page 77 Number of SIO output ON times integration function
Ex.
When the output ON times integration value is read from the device connected to channel 1 when the Q terminal of the output
port is turned on five times, 0005H is stored in the third and fourth bytes.
■
Process data size
Configure the swap setting and process data size for each channel.
For the process data size, specify the number of words not less than the process data size of the IO-Link device used. (If the
IO-Link device controls 3-byte process data, set the process data size to two words (4 bytes) or more.)
The following table shows the swap setting and process data size of each channel.
• Process data size: Specify the number of words for the process data size.
• Swap setting: Enable/disable the swap function.
For details on the swap function, refer to the following.
Item
Description
Access code
13H
Attribute code
05H
Address code
00H to 07H (corresponding to channel numbers 1 to 8)
Data size
4 bytes
Data
• First and second bytes: The output ON times integration value of the CQ terminal (0 to 65535) (Default: 0000H)
• Third and fourth bytes: The output ON times integration value of the Q terminal (0 to 65535) (Default: 0000H)
Item
Description
Access code
20H
Attribute code
05H
Address code
00H
Data size
8 bytes
Data
• First byte: The swap setting and process data size of the IO-Link module channel 1 (Default: 01H)
• Second byte: The swap setting and process data size of the IO-Link module channel 2 (Default: 01H)
• Third byte: The swap setting and process data size of the IO-Link module channel 3 (Default: 01H)
• Fourth byte: The swap setting and process data size of the IO-Link module channel 4 (Default: 01H)
• Fifth byte: The swap setting and process data size of the IO-Link module channel 5 (Default: 01H)
• Sixth byte: The swap setting and process data size of the IO-Link module channel 6 (Default: 01H)
• Seventh byte: The swap setting and process data size of the IO-Link module channel 7 (Default: 01H)
• Eighth byte: The swap setting and process data size of the IO-Link module channel 8 (Default: 01H)
Data configuration
Description
b0 to b4
Process data size (1 to 16) (Unit: words)
B5, b6
Use prohibited (fixed to 0)
b7
Swap setting (0: Disabled, 1: Enabled)
Summary of Contents for CC-Link IE Field NZ2GF12A-60IOLH8
Page 1: ...CC Link IE Field Network Waterproof Remote IO Link Module User s Manual NZ2GF12A 60IOLH8 ...
Page 2: ......
Page 30: ...28 3 PROCEDURES BEFORE OPERATION MEMO ...
Page 100: ...98 8 MODULE FUNCTION BLOCKS MEMO ...
Page 109: ...9 PROGRAMMING 9 2 Program Example of Setting Parameters Using a Dedicated Instruction 107 9 ...
Page 116: ...114 9 PROGRAMMING 9 3 Example of Program to Communicate with an IO Link Device ...
Page 118: ...116 10 MAINTENANCE AND INSPECTION MEMO ...
Page 155: ...APPX Appendix 7 Additional or Changed Functions 153 A MEMO ...
Page 157: ...I 155 MEMO ...
Page 161: ......