MSI-3750 Digital Weight Indicator
◆
User Guide
➀
EXIT
F2
➠
➀
EXIT
F2
SETPT 2
➁
ENTER
➂
F5
√
UV
F3
VALUE
➄
ENTER
GREATER
≈
UV
F3
LESSTHAN
1)
Use the
UP
or
DOWN
key to scroll to the
set point (1-8) you wish to program.
2)
Push the
ENTER
key. You are now in the
“SET POINTS PROGRAM MENU”. The
LCD indicates if the set point is active
(ON) or inactive (OFF).
In this example we’ll program set point 2,
but the procedure applies for any set point.
3)
Use the
LEFT
or
RIGHT
cursor key to
enable the set point. Dual Input 3750s: Use
the
LEFT
or
RIGHT
Cursor keys to select
A, B, A or B, A Ad b (Summed A+B)
4)
The next step is to assign a weight value to
the set point. Use the
UP
key (if necessary)
to scroll to the “VALUE” menu.
5)
Push
ENTER
.
6)
For a set point that will switch on when the
weight is greater than or equal to the value
motor or solenoid. This can be prevented by using a dead zone to cause the set
point to have one value for turning on, and a different value for turning off. For
example: A set point set to
≥
500 lb with a dead zone of 10 lb will turn on at
≥
500 lb. It will not turn off until the weight goes below 490 lb (500–10). A set
point set to
≤
750 lb with a dead zone of 20 lb will turn on when the weight is
≤
750 lb. It will not turn off until the weight is
≥
770 lb (750+20).
Note: A Dead Zone value of zero is equal to 1/2 “d”.
SP LATCH MENU
The set point Latch Menu is used to latch the set point relay on until it is cleared
manually. There are two standard ways to clear a latched set point:
1)
Program a function key to “RESET SP”.
2)
Turn the 3750 off, then on again.
USING SET POINTS
Set Point Entry Procedure
You must first be in the SETUP SET POINTS menu to proceed. See procedure above.