Function library
Torque (torque control)
Setpoint processing
352
EDBCSXS064 EN 4.0
12.28.3.3
Influencing the ramp function generator
ƒ
If the controller is inhibited, the ramp function generator accepts the actual speed
and passes it to the downstream function. This function has priority over all other
functions.
ƒ
If the input TORQUE−NSET.RfgStop = TRUE (C7511/8), the ramp function generator is
stopped. Changes of the input of the ramp function generator have no effect on the
output signal.
ƒ
If the input TORQUE−NSET.Rfg0 = TRUE (C7511/3) the ramp function generator
reaches zero along the deceleration ramp.
ƒ
The threshold in C0241 specifies when the message "Setpoint reached" is output.
On the ramp function generator for the torque setpoint, the following applies: input
signal = output signal
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
C0241 NSET RFG I = O
1.00
Threshold for message "Setpoint
reached"
On the ramp function generator
for
l
speed setpoint (for "speed
control")
l
torque setpoint (for "torque
control")
input signal = output signal.
352
0.00
{0.01 %}
100.00 100 % = n
max