Appendix
Code table
378
EDBCSXS064 EN 4.0
IMPORTANT
Possible settings
Code
Selection
Lenze/
{Appl.}
Designation
No.
C0178 Op timer
Running time meter
Read only
0
{1 sec}
4294967295 Time when the controller was
enabled
C0179 Mains timer
Power−on time meter
Only display
0
{1 sec}
4294967295 Time when the mains was
switched on
C0182 Ti S−shaped
20.00
Form of the S−curve for the
l
speed setpoint (for "speed
control")
l
torque setpoint (for "torque
control")
of the ramp function generator
(C0134 = 1)
0.01
{0.01 s}
50.00 The higher the value, the bigger
the S−rounding.
C0183 Diagnostics
Drive diagnostics
Read only
l
Indicates fault or status
information
l
If several fault or status
information are to be shown
at the same time, the
information with the smallest
number is displayed
0
OK
No fault
101
Initialisation phase
102
TRIP/trouble
103
Emergency stop activated
104
IMP message
105
Power off
111
Operation inhibit C0135
112
Operation inhibit AIF
113
Operation inhibit CAN
121
Controller inhibit via X6/SI1
122
Internal controller inhibit 1
123
Internal controller inhibit 2
124
Controller inhibit via STOP key of the
keypad
125
Controller inhibit via AIF
126
Controller inhibit via CAN
131
Fail QSP
141
Restart protection
142
Pulse inhibit
High resistance power outputs
151
Quick stop (QSP) via terminal
152
Quick stop (QSP) via STOP key of the
keypad
153
Quick stop (QSP) via AIF
154
Quick stop (QSP) via CAN
160
PLC Stop
PLC must be started.
250
Warning