Technical data
General data and operating conditions
32
EDBCSXS064 EN 4.0
General electrical data
EMC
Compliance with the requirements acc. to EN 61800−3
Noise emission
Compliance with the limit class C2 acc. to EN 61800−3
(achieved by using collective filters typical for the application)
Noise immunity
Requirements acc. to EN 61800−3
Requirement
Standard
Severity
ESD
1)
EN 61000−4−2
3, i. e.
l
8 kV for air discharge
l
6 kV for contact discharge
Conducted high frequency
EN 61000−4−6
10 V; 0.15 ... 80 MHz
RF interference (housing)
EN 61000−4−3
3, i. e. 10 V/m;
80 ... 1000 MHz
Burst
EN 61000−4−4
3/4, i. e. 2 kV/5 kHz
Surge (surge voltage on mains
cable)
EN 61000−4−5
3, i. e. 1.2/50
m
s
l
1 kV phase/phase
l
2 kV phase/PE
Insulation resistance
EN61800−5−1, UL840: Overvoltage category III
Discharge current to PE
(Acc. to EN 61800−5−1)
> 3.5 mA AC
Enclosure
IP20 for
l
Standard installation (built−in unit)
l
Cold−plate technique
l
Mounting with thermal separation (push−through technique), IP54 on heatsink side
Protective measures against
l
Short circuit in power terminals
– Motor terminal has a limited protection against short circuit (after short circuit
detection, the error message must be reset.)
l
Short circuit in auxiliary circuits
– Digital outputs: Short−circuit−proof
– Bus and encoder systems: Limited protection against short circuit (if necessary,
monitoring functions can be switched off, in this case, error messages must be
reset:)
l
Earth fault (earth−fault protected during operation, limited earth−fault protection
on mains power−up)
l
Overvoltage
l
Motor stalling
l
Motor overtemperature (input for KTY, I
2
x t monitoring)
Protective insulation of control circuits
Protective separation from the mains
Double/reinforced insulation acc. to EN 61800−5−1
1)
Noise immunity in the above−mentioned severities must be guaranteed by the control cabinet! The user
must check the compliance with the severities!