Appendix
Code table
372
EDBCSXS064 EN 4.0
IMPORTANT
Possible settings
Code
Selection
Lenze/
{Appl.}
Designation
No.
C0124 OH5 limit
75
Threshold for temperature
monitoring inside the device
10
{1 %}
90 C0062 > C0124
ð
fault message
OH5 (C0605)
C0125 Baud rate
0
Baud rate for operation via AIF
interface X1
0
9600 bit/s
Communication modules on AIF
interface X1:
l
LECOM−A/B/LI 2102
l
PROFIBUS−DP 2133
1
4800 bits/s
2
2400 bit/s
3
1200 bit/s
4
19200 bit/s
C0126 MONIT CE0
3
Fault response regarding the
monitoring of communication
via AIF interface X1.
l
Via C2382 you can select
whether controller inhibit
(CINH) or quick stop (QSP) is
activated when a CE0 fault
occurs.
0
TRIP
A communication error activates
the CE0 response set.
2
Warning
3
Off
Monitoring switched off.
C0127 OC8 limit
100
Threshold for I
2
x t warning
(motor)
0
{1 %}
120 I
2
x t > C0127
ð
fault message
OC8 (C0606)
C0128 Tau motor
5.0
Thermal time constant of the
motor
0.5
{0.1 min}
25.0 For calculating the I
2
x t
disconnection
C0129 Charc.: Ix/Nx
Reduction of the speed/torque
characteristic for UL−compliant
thermal motor monitoring (I
2
x t)
The reduced speed/torque
characteristic reduces the
permissible thermal load of
self−ventilated standard motors.
1
100
10
{1 %}
200 S1 torque characteristic I
1
/I
rated
This value also enables an
increase of the maximally
permissible utilisation.
2
40
S1 torque characteristics
n
2
/n
rated
With increasing speeds, the
maximally permissible
utilisation remains unchanged
(I
Mot
= I
rated
).