Configuration
Remote parameterisation (gateway function)
190
EDBCSXS064 EN 4.0
8.5
Remote parameterisation (gateway function)
From operating system V6.x onwards, the axis module supports the remote
parameterisation of other fieldbus nodes. Then, all write/read accesses to parameters are
not executed anymore in the axis module but redirected to the bus node selected for
remote maintenance.
ƒ
The redirection takes place via the parameter data channel SDO1 of the selected
node.
ƒ
The node to which the write/read accesses is to be redirected, is determined with
the corresponding node address via C0370.
(C0370 = 0: remote parameterisation deactivated)
ƒ
With C0371 = 1, determine the interface X14 (CAN−AUX) of the axis module as
gateway channel.
ƒ
Use C2470 (CAN−AUX) to select the transmission channel for reading and writing
parameter data.
ƒ
A time−out during remote parameterisation activates the system error message
"CE15". The corresponding response can be configured under C2485 (
Code
Possible settings
IMPORTANT
No.
Designation
Lenze/
{Appl.}
Selection
[C0370] SDO gateway
0
Activate address
gateway/remote
parameterisation
l
C0370
¹
0: All code
write/read accesses are
redirected to the CAN node
with the CAN node address
set here.
l
The corresponding code is
accessed via parameter data
channel 1 of the target device.
l
C0370 = 0: remote
parameterisation is
deactivated
190
0
{1}
63
C0371 Gateway Ch.
1
Selection of the gateway channel
190
0
CAN
Use CAN bus interface X4
1
CAN−AUX
Use CAN bus interface X14
C2470 ParWrite
0
CANaux channel used by
L_ParWrite/L_ParRead
(byComChannel = 11)
190
0
Unused PDO channel free for
reconfiguration
(CANaux1...3_IN/CANaux1...3_OUT)
1
Parameter data channel 2