User Action:
Information only; no action is required
•
FQXSPPW0009I: [PowerSupplyElementName] has been Power Cycled.
This message is for the use case when an implementation has detected a Power Unit that has been power
cycled.
Severity: Info
Serviceable: No
Automatically notify Support: No
Alert Category: System - Other
SNMP Trap ID:
CIM Prefix: PLAT CIM ID: 0108
User Action:
Information only; no action is required
•
FQXSPPW0031J: Numeric sensor [NumericSensorElementName] going low (lower non-critical) has
asserted.
This message is for the use case when an implementation has detected a Lower Non-critical sensor going
low has asserted.
Severity: Warning
Serviceable: Yes
Automatically notify Support: No
Alert Category: Warning - Voltage
SNMP Trap ID: 13
CIM Prefix: PLAT CIM ID: 0476
User Action:
CMOS battery is recommended to replace with new one.
•
FQXSPPW0035M: Numeric sensor [NumericSensorElementName] going low (lower critical) has
asserted.
This message is for the use case when an implementation has detected a Lower Critical sensor going low
has asserted.
Severity: Error
Serviceable: Yes
Automatically notify Support: Yes
Alert Category: Critical - Voltage
SNMP Trap ID: 1
CIM Prefix: PLAT CIM ID: 0480
User Action:
Use one of the following procedures:
1. If the specified sensor is Planar 3.3V or Planar 5V, (trained technician only)replace the system board.
2. If the specified sensor is Planar 12V, check the System Management Module or xClarify Controller
event log for power-supply-related issues, and resolve those issues.
3. If the problem remains, replace (trained technician only)the system board.
•
FQXSPPW0047M: Numeric sensor [NumericSensorElementName] going high (upper critical) has
asserted.
.
113