Technical data
Operating manual INVEOR
79
7
Technical data
7.1
General data
This chapter contains the technical data.
Installation size
MA
MB
MC
MD
Rated motor power [kW]
(4-pol asynchr. motor)
0,55 0,75
1,1 1,5 2,2 3 4 5,5 7,5 11 15 18,5 22
Ambient temperature [°C]
-25 (non condensing) bis +50 (without derating) *
Mains voltage [V]
3~ 200 -10% ... 480 +10%
Mains frequency [Hz]
47 bis 63
Network configurations
TN/TT
Line
current
[A]
1,4 1,9 2,6 3,3 4,6 6,2 7,9 10,8 14,8 23,3
28,3 33,3 39,9
Nominalcurrent, eff.
[I
N
at 8kHz/400 V]
1,7 2,3 3,1 4,0 5,6 7,5 9,5 13,0 17,8 28,0
34,0 40,0 48,0
Min. brake resistance [
Ω
] 100
50 50
30
Max. current, eff.
150% of the nominal current for 60 sec
130%
Switching frequency [kHz]
4, 8, 16, (factory setting 8)
Rotating field frequency [Hz]
0 - 400
Protective function
Undervoltage, Overvoltage, I
2
t restriction, short circuit, motor –inverter temperature, anti-tilt
protection, stall protection
Process control
PID controller, free configuration
Dimensions
[L x W x H] mm
233 x 153 x 120
270 x 189 x 133
307x223x181
414 x 294 x 238
Weight including adapter
plate [kg]
3,9 5,0
8,7
21,0
Protection type [IPxy]
65
EMC
approvals acc. to DIN EN 61800-3, class C2
Tab. 10: Technical data (technical changes reserved)
* in terms of the UL 508C standard, please see chapter 9.4!
Summary of Contents for INVEOR MA
Page 1: ...Operating manual INVEOR Betriebsanleitung_INVEOR_A5 indd 1 28 02 11 10 33...
Page 91: ...Guidelines Norms and Standards Operating manual INVEOR 91...
Page 92: ...Guidelines Norms and Standards 92 Operating manual INVEOR...
Page 93: ...Guidelines Norms and Standards Operating manual INVEOR 93...