Parameters
Operating manual INVEOR
61
4.152/4.172
DOx off
Unit:
min: 0
max.:1,000,000
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
4,150/4,170
If the set process value exceeds the switch-on limit, the output is set to 1.
5.3.9
Relay
For relays 1 and 2 (Rel.x – display Rel. 1/Rel. 2)
4.190/4.210
Rel.x function
Unit: integer
min: 0
max.: 500
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
4,191/4,211
4,192/4,212
Selection of the process value to which the output should switch.
0= not allocated / INVEOR Soft-PLC
1= DC bus voltage
2= line voltage
3= motor voltage
4= motor current
5= frequency feedback
6= –
7= –
8= IGBT temperature
9= internal temperature
10= error (NO)
11= inverted error (NC)
12= final release levels
13= digital input1
14= digital input 2
15= digital input 3
16= digital input 4
17= ready for operation
18= ready
19= operation
20= ready for ope ready
21= ready for ope ready + operation
22= ready + operation
23 = motor power
24 = torque
25 = field bus
50 = motor current limit active
Summary of Contents for INVEOR MA
Page 1: ...Operating manual INVEOR Betriebsanleitung_INVEOR_A5 indd 1 28 02 11 10 33...
Page 91: ...Guidelines Norms and Standards Operating manual INVEOR 91...
Page 92: ...Guidelines Norms and Standards 92 Operating manual INVEOR...
Page 93: ...Guidelines Norms and Standards Operating manual INVEOR 93...