5.4.3
Switching frequency
The internal switching frequency (clocking frequency) can be changed in
order to control the power element. A high setting reduces noise in the motor
but increases EMV emission and losses in the drive control.
34.030
Switching frequency
Unit: Hz
min: 1
max.: 4
Parameter manual:
p. xy
Transfer status:
2
def.: 2
own value (
to
be entered!
)
Relationship to
parameter:
Selection of the switching frequency for the inverter
1 = 16 kHz
2 = 8 kHz
4 = 4 kHz
5.4.4
Controller data
34.010
Control method
Unit: integer
min: 100
max.: 200
Parameter manual:
p. xy
Transfer status:
2
def.: 100
Own value (
to
be entered!
)
Relationship to
parameter:
33,001
34,011
Selection of the type of control.
100 = open-loop asynchronous motor
101 = close-loop asynchronous motor
200 = open-loop synchronous motor
201 = close-loop synchronous motor