Parameters
Operating manual INVEOR
53
2.153
MOP response time
Unit: s
min: 0.02
max.: 1000
Parameter manual:
p. xy
Transfer status:
2
def.: 0.3
Own value (
to
be entered!
)
Relationship to
parameter:
Indicates the time for which the signal is considered permanent.
2.154
MOP reference memory
Unit: integer
min: 0
max.: 1
Parameter manual:
p. xy
Transfer status:
2
def.: 0
Own value (
to
be entered!
)
Relationship to
parameter:
Defines whether the target value of the motor potentiometer is retained even
after power outage.
0 = disable
1 = enable
5.3.4
PID process controller
This mode has to be selected in parameter 1,100,
the target value source has to be selected in parameter 1,130,
see also chapter 5.2.1, “Explanation of operating modes – preset speed”.
3.050
PID proportional gain
Unit:
min: 0
max.: 100
Parameter manual:
p. xy
Transfer status:
2
def.: 1
own value (
to
be entered!
)
Relationship to
parameter:
1,100
1,130
proportional share of PID controller
3.051
PID integral gain
Unit: 1/s
min: 0
max.: 100
Parameter manual:
p. xy
Transfer status:
2
def.: 1
own value (
to
be entered!
)
Relationship to
parameter:
1,100
1,130
integral share of PID controller
Summary of Contents for INVEOR MA
Page 1: ...Operating manual INVEOR Betriebsanleitung_INVEOR_A5 indd 1 28 02 11 10 33...
Page 91: ...Guidelines Norms and Standards Operating manual INVEOR 91...
Page 92: ...Guidelines Norms and Standards 92 Operating manual INVEOR...
Page 93: ...Guidelines Norms and Standards Operating manual INVEOR 93...