Parameters
Operating manual INVEOR
45
5.3
Application parameters
5.3.1
Basic parameters
1.020
Low speed
Unit: Hz
min: 0
max.: 400
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
1,150
3,070
The low speed is the frequency provided by the drive control as soon as it
released and no additional target value is pending.
This frequency is not reached if
a) acceleration is carried out while the drive is not moving.
b) the frequency inverter is blocked. The frequency is then reduced to 0 Hz
before it is blocked.
c) the frequency inverter reverses (1,150). The revolving field is reversed at 0
Hz.
d) the stand-by function (3,070) is active.
1.021
High speed
Unit: Hz
min: 5
max.: 400
Parameter manual:
p. xy
Transfer status:
2
def.: 50
own value (
to
be entered!
)
Relationship to
parameter:
1,050
1,051
The high speed is the frequency produced by the inverter in dependence on
the reference.
1.050
Deceleration 1:
Unit: s
min: 0,1
max.: 1000
Parameter manual:
p. xy
Transfer status:
2
def.: 5
own value (
to
be entered!
)
Relationship to
parameter:
1,021
1,054
Deceleration 1 is the time that the inverter takes to brake to 0 Hz from the
high speed (1,021).
If the set deceleration time cannot be reached, the fastest possible
deceleration time is implemented.
Summary of Contents for INVEOR MA
Page 1: ...Operating manual INVEOR Betriebsanleitung_INVEOR_A5 indd 1 28 02 11 10 33...
Page 91: ...Guidelines Norms and Standards Operating manual INVEOR 91...
Page 92: ...Guidelines Norms and Standards 92 Operating manual INVEOR...
Page 93: ...Guidelines Norms and Standards Operating manual INVEOR 93...