Installation
Operating manual INVEOR
21
3.2.5
Wiring instructions
The control connections of the application card are located inside the drive
control.
The configuration can vary, depending on the version.
Terminals:
Plug terminal clamp with activation button
(slot screwdriver, max. width 2.5 mm)
Connection cross-section:
0.5 to 1.5 mm
2
, single-wire, AWG 20 to
AWG 14
Connection cross-section:
0.75 to 1.5 mm
2
, fine-wired, AWG 18 to
AWG 14
Connection cross-section:
0.5 to 1.0 mm
2
, fine-wired, (core end sleeves
with and without plastic collar)
Length of stripped insulation:
9 to 10 mm
The terminals for the mains cable are located inside the drive control. The
INVEOR also has the option of being equipped with terminals for connecting
a brake resistor.
The configuration can vary, depending on the version.
Core end sleeves with plastic collars and lugs are recommended.
Terminals:
Spring force connection
(slot screwdriver, max. width 2.5 mm)
Connection cross-section: 0.2 to 10 mm
2
, rigid, 0.2 to 6 mm
2
, flexible
Connection cross-section: 0.25 to 6 mm
2
(core end sleeves without plastic collar)
Connection cross-section: 0.25 to 4 mm
2
(core end sleeves with plastic collar)
Connection cross-section: 0.25 to 1.5 mm
2
for 2 conductors of the same
cross-section
(twin-core end sleeves with plastic collar)
Conductor cross-section: AWG 24 to AWG 8
Length of stripped insulation:
15 mm
Summary of Contents for INVEOR MA
Page 1: ...Operating manual INVEOR Betriebsanleitung_INVEOR_A5 indd 1 28 02 11 10 33...
Page 91: ...Guidelines Norms and Standards Operating manual INVEOR 91...
Page 92: ...Guidelines Norms and Standards 92 Operating manual INVEOR...
Page 93: ...Guidelines Norms and Standards Operating manual INVEOR 93...