3.069
PID peset reference mode
Unit: integer
min: 0
max.: 2
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
1,100
3,062 to 3,068
Selection of the digital inputs used for fixed frequencies
0 = Digital In 1
(PID preset reference 1) (3,062)
1 = Digital In 1, 2 (PID preset references 1 – 3) (3,062 to 3,064)
2 = Digital In 1, 2, 3 (PID preset references 1 – 7) (3,062 to 3,068)
3.070
PID stand-by time
Unit: s
min: 0
max.: 10000
Parameter manual:
S. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
1,020
If the drive control operates the set time with the low speed (parameter
1,020), the motor is stopped (0 Hz), see also Chapter 5.2.1, “PID process
control”
0
= disable
> 0
= waiting time until stand-by function is enabled
3.071
PID stand-by hysteresis
Unit: %
min: 0
max.: 50
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
3,060
Condition for waking up the PID controller from stand-by.
Once the control difference exceeds the set value in %, the control begins
again, see also “Control mode (parameter 1,100) – PID controller”.
Summary of Contents for INVEOR MA
Page 1: ...Operating manual INVEOR Betriebsanleitung_INVEOR_A5 indd 1 28 02 11 10 33...
Page 91: ...Guidelines Norms and Standards Operating manual INVEOR 91...
Page 92: ...Guidelines Norms and Standards 92 Operating manual INVEOR...
Page 93: ...Guidelines Norms and Standards Operating manual INVEOR 93...