Parameters
50
Operating manual INVEOR
1.180
Reset
Unit: integer
min: 0
max.: 4
Parameter manual:
p. xy
Transfer status:
2
def.: 4
own value (
to
be entered!
)
Relationship to
parameter:
1,181
1,182
Selection of the source for error confirmation.
Errors can only be confirmed once the error has been removed.
Some errors can only be confirmed by switching the control off and then on
again,
see list of errors.
Auto-confirmation via parameter 1,181.
0 = no manual confirmation possible
1 = rising shoulder at digital input 1
2 = rising shoulder at digital input 2
3 = rising shoulder at digital input 3
4 = rising shoulder at digital input 4
1.181
Automatic reset
Unit: s
min: 0
max.:1,000,000
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
1,180
1,182
Next to the reset function (1,180), an automatic reset can be selected.
0
= no automatic confirmation
> 0
= time for automatic reset of error in seconds
1.182
Quantity of automatic reset
Unit:
min: 0
max.: 500
Parameter manual:
p. xy
Transfer status:
2
def.: 5
own value (
to
be entered!
)
Relationship to
parameter:
1,180
1,181
Next to the automatic reset (1,181), it is possible to limit the number of
maximum automatic resets here.
0
= no restriction of automatic confirmations
> 0
= number of maximum permitted automatic confirmations
Summary of Contents for INVEOR MA
Page 1: ...Operating manual INVEOR Betriebsanleitung_INVEOR_A5 indd 1 28 02 11 10 33...
Page 91: ...Guidelines Norms and Standards Operating manual INVEOR 91...
Page 92: ...Guidelines Norms and Standards 92 Operating manual INVEOR...
Page 93: ...Guidelines Norms and Standards Operating manual INVEOR 93...