![Kostal INVEOR MA Operating Manual Download Page 27](http://html1.mh-extra.com/html/kostal/inveor-ma/inveor-ma_operating-manual_1999368027.webp)
Installation
Operating manual INVEOR
27
Terminal
no.
Designation
Configuration
1
24 V In
ext. power supply
2 GND
(ground) Mass
3
24 V Out
int. power supply
4 GND
(ground) Mass
5
24 V Out
int. power supply
6
Dig. In 1
Target value release
(parameter 1,131)
7
Dig. In 2
Free (not allocated)
8
Dig. In 3
Free (not allocated)
9
Dig. In 4
Error reset
(parameter 1,180)
10
En-HW (release)
Hardware release
11
Dig. Out 1
Fault message
(parameter 4,150)
12
Dig. Out 2
Free (not allocated)
13
A. Out 0 ... 20 mA
Actual frequency
(parameter 4,100)
14
10 V Out
for ext. voltage divider
15
A. Out 0 ... 10 V
Actual frequency
(parameter 4,100)
16
A GND (ground 10 V)
Mass
17
A. In 1
Analogue input 1
18
A GND (ground 10 V)
Mass
19
A. In 2
Analogue input 2
20
A GND (ground 10 V)
Mass
Tab. 4:
Terminal configuration X5