Parameters
56
Operating manual INVEOR
5.3.5
Analogue inputs
For analogue inputs 1 and 2 (Alx display Al1/Al2)
4.020/4.050
Alx reference type
Unit: integer
min: 0
max.: 1
Parameter manual:
p. xy
Transfer status:
2
def.: 1
own value (
to
be entered!
)
Relationship to
parameter:
Function of analogue inputs 1/2:
1 = voltage input
2 = current input
4.021/4.051
Alx minimum input
Unit: %
min: 0
max.: 100
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
Specifies the minimum value of the analogue inputs as a percentage of the
final area value.
Example: 0…10 V or 0…20 mA = 0%…100%
2…10 V or 4…20 mA = 20%…100%
4.022/4.052
Alx maximum input
Unit: %
min: 0
max.: 100
Parameter manual:
p. xy
Transfer status:
2
def.: 100
own value (
to
be entered!
)
Relationship to
parameter:
Specifies the maximum value of the analogue inputs as a percentage of the
final area value.
Example: 0…10 V or 0…20 mA = 0%…100%
2…10 V or 4…20 mA = 20%…100%
4.023/4.053
Alx dead time
Unit: %
min: 0
max.: 100
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
Dead time in percentage of the final area value of the analogue inputs.
Summary of Contents for INVEOR MA
Page 1: ...Operating manual INVEOR Betriebsanleitung_INVEOR_A5 indd 1 28 02 11 10 33...
Page 91: ...Guidelines Norms and Standards Operating manual INVEOR 91...
Page 92: ...Guidelines Norms and Standards 92 Operating manual INVEOR...
Page 93: ...Guidelines Norms and Standards Operating manual INVEOR 93...