86
Function
code
Name
Descriptions
Unit
Factory
setting
Modif.
Setting
range
1:Enable
Ten’s place of LED:
Action selection for auto reset
interval fault indication.
0:Disable
1:Enable
Hundred’s place of LED:
Selection for fault locked function.
0:Disable
1:Enable
Thousand’place of LED:
Reserved
A8.01
Fault masking
selection 1
Unit’s place of LED:
Communication fault masking
selection
Ten’s place of LED:
Relay faultmasking selection
Hundred’s place of LED:
EEPROMfault masking selection
Thousand’s place of LED:
Reserved
0:Disable.Stop when fault
happen
1:Disable.Continue operating
when fault happen
2:Enable
1
0000
×
0~2222H
A8.02
Fault masking
selection 2
Unit’s place of LED:
Open phase fault masking selection
for input
Ten’s place of LED:
Open phase fault masking selection
for output
0:Disable.Stop when fault happen
1:Disable.Continue operating when
fault happen
2:Enable
1
00
×
0~22H
A8.03
Motor overload
0: Disabled
1
1
×
0~2