38
Setting
Function
Setting
Function
0
Drive running
signal (RUN)
1
Frequency arriving
signal (FAR)
2
Frequency
detection
threshold
(FDT1)
3
Frequency detection
threshold (FDT2)
4
Reserved
5
Low voltage
lock-up signal (LU)
6
External
stopping
command
(EXT)
7
High limit of
frequency (FHL)
8
Lower limit of
frequency
(FLL)
9
Zero-speed running
10
Reserved
11
Reserved
12
PLC running
step finish
signal
13
PLC running cycle
finish signal
14
Swing limit
15
Drive ready (RDY)
16
Drive fails
17
Reserved
18
Reserved
19
Torque limiting
20
Drive running
forward/reverse
21
Timer 1 reach
22
Timer 2 reach
23
Counter reach
24
Intermediate
counter reach
The instructions of the functions in Table 6-6 as
following:
0: Drive running signal (RUN)
When the drive is in operating status, there will be
running indication signal output by this terminal.
1: Frequency arriving signal (FAR)
See A6.19.
2: Frequency detection threshold (FDT1)
See A6.20~A6.21.
3: Frequency detection threshold (FDT2)
See A6.22~A6.23.
4: Reserved.
5: Low voltage lock-up signal (LU)
The terminal outputs the indicating signal if the DC bus
voltage is lower than the low voltage limit, and the LED
displays “P.oFF”.
6: External stopping command (EXT)
The terminal outputs the indicating signal if the drive
outputs tripping signal caused by external fault (E015).
7: High limit of frequency (FHL)
The terminal outputs the indicating signal if the preset
frequency is higher than upper limit of frequency and the
operating frequency reaches the upper limit of
frequency.
8: Lower limit of frequency (FLL)
The terminal outputs the indicating signal if the preset
frequency is higher than lower limit of frequency and the
operating frequency reaches the lower limit of
frequency.
9: Zero-speed running
The terminal outputs the indicating signal if the drive’s
output frequency is 0 and the drive is in operating status.
10~14:Reserved.
15: drive ready (RDY)
If RDY signal is output, it means the drive has no fault,
its DC bus voltage is normal and it can receive starting
command.
16: Drive fails
The terminal outputs the indicating signal if the drive
has faults.
17~18: Reserved.
19: Torque limiting
The terminal outputs the indicating signal if the torque
reach drive torque limit or brake torque limit.
20: Drive running forward/reverse
The terminal outputs the indicating signal according to
the drive’s current running direction.
21
:
Timer 1 reach
22
:
Timer 2 reach